電纜橋架是不是一定要接地

  電纜橋架需要接地嗎?

  Do cable trays need to be grounded?

  電纜橋架需要接地,看看截止2023年有關橋架接地的相關標準:

  Cable trays need to be grounded. Please refer to the relevant national standards for tray grounding as of 2023

  《GB?50303-2015 建筑電氣工程施工質量驗收規(guī)范》

  GB 50303-2015 Code for Acceptance of Construction Quality of Building Electrical Engineering

  11 梯架、托盤和槽盒安裝

  Installation of 11 ladder frames, trays, and trough boxes

  11.1 主控項目(強制條文,必須嚴格執(zhí)行)

  11.1 Main control items (mandatory provisions, must be strictly enforced)

  11.1.1金屬梯架、托盤或槽盒本體之間的連接應牢固可靠,與保護導體的連接應符合下列規(guī)定:

  11.1.1 The connection between metal ladder frames, trays or trough boxes should be firm and reliable, and the connection with protective conductors should comply with the following regulations:

  1、梯架、托盤和槽盒全長不大于30m時,不應少于2處與保護導體可靠連接;全長大于30m時,每隔20m~30m應增加一個連接點。起始端和終點端均應可靠接地。

  1. When the total length of the ladder, tray, and trough box is not more than 30m, there should be no less than 2 reliable connections with the protective conductor; When the total length is greater than 30m, a connection point should be added every 20m~30m. Both the starting and ending ends should be reliably grounded.

  2、非鍍鋅梯架、托盤和槽盒本體之間連接板的兩端應跨接保護聯(lián)結導體,保護聯(lián)結導體的截面積應符合設計要求。

  2. The two ends of the connecting plate between the non galvanized ladder frame, tray, and trough box body should be bridged with protective connecting conductors, and the cross-sectional area of the protective connecting conductors should meet the design requirements.

  3、鍍鋅梯架、托盤和槽盒本體之間不跨接保護聯(lián)結導體時,連接板每端不應少于2個有防松螺帽或防松墊圈的連接固定螺栓。

  3. When the galvanized ladder frame, tray, and trough box body do not cross connect the protective connecting conductor, there should be no less than 2 connection fixing bolts with anti loosening nuts or anti loosening washers at each end of the connecting plate.

  《T/CECS 31-2017 鋼制電纜橋架工程技術規(guī)程》

  Technical Specification for Steel Cable Tray Engineering (T/CECS 31-2017)

  4.8接 地

  4.8 Grounding

  4.8.1 鋼制電纜橋架系統(tǒng)的起始端和終端應與建筑物接地裝置可靠連接,全長大于30m時,每隔20m?30m應增加一個接地連接點。

  4.8.1 The starting and ending ends of the steel cable tray system should be reliably connected to the building grounding device. When the total length is greater than 30m, every 20m? An additional grounding connection point should be added for 30m.

  4.8.2 在伸縮縫或連續(xù)鉸鏈連接處應采用銅軟導線或編織銅線連接,其截面積不應小于16mm2

  4.8.2 Copper flexible wires or braided copper wires should be used at expansion joints or continuous hinge connections, with a cross-sectional area of not less than 16mm2

  4.8.3 鋼制電纜橋架在岀入建筑物時,應就近與總等電位接地裝 置進行聯(lián)結。

  4.8.3 When steel cable trays enter or exit buildings, they should be connected to the nearest main equipotential grounding device.

  GB50169-2016《 電氣裝置安裝工程接地裝置施工及驗收規(guī)范?》

  GB50169-2016 Code for Construction and Acceptance of Grounding Devices in Electrical Equipment Installation Engineering

  3.0.4??電氣裝置的下列金屬部分,均必須接地:(強制條文,必須嚴格執(zhí)行)

  3.0.4?? The following metal parts of electrical devices must be grounded: (Mandatory provisions must be strictly enforced)

  7??電纜橋架、支架和井架。

  7. Cable trays, brackets, and derricks.

  GB51348-2019《民用建筑電氣設計標準》

  GB51348-2019 "Electrical Design Standard for Civil Buildings"

  8.5??電纜橋架布線

  8.5?? Cable tray wiring

  8.5.18??金屬電纜橋架應與保護聯(lián)結導體可靠連接,且全長不應少于2處接地。高分子合金電纜橋架、玻璃鋼橋架可不接地

  8.5.18?? The metal cable tray should be reliably connected to the protective bonding conductor, and the total length should not be less than 2 grounding points. Polymer alloy cable trays and fiberglass cable trays may not be grounded

  GB50606-2010 《 智能建筑工程施工規(guī)范?》

  GB50606-2010 "Code for Construction of Intelligent Building Engineering"

  13.2??設備安裝

  13.2?? equipment installation

  13.2.1??橋架、管線敷設除應執(zhí)行現(xiàn)行標準《火災自動報警系統(tǒng)施工及驗收規(guī)范》GB?50166—2007第3.2節(jié)的規(guī)定和本規(guī)范第4章的規(guī)定外,尚應符合下列規(guī)定:

  13.2.1?? The installation of cable trays and pipelines should comply with the current national standard "Code for Construction and Acceptance of Automatic Fire Alarm Systems" GB? In addition to the provisions of Section 3.2 of 50166-2007 and Chapter 4 of this specification, the following provisions shall also be complied with:

  3??橋架、金屬線管應作保護接地。

  3. Cable trays and metal conduits should be protected by grounding.

  4.5??質量控制

  4.5?? Quality Control

  4.5.1??主控項目應符合下列規(guī)定:

  4.5.1?? The main control project shall comply with the following regulations:

  4??橋架、線管及接線盒應可靠接地;當采用聯(lián)合接地時,接地電阻不應大于1Ω

  4. Cable trays, conduits, and junction boxes should be reliably grounded; When using joint grounding, the grounding resistance should not exceed 1 Ω

  GB50168-2018《 電氣裝置安裝工程電纜線路施工及驗收標準?》

  GB50168-2018 "Construction and Acceptance Standards for Cable Lines in Electrical Equipment Installation Engineering

  5.2電纜支架的配制與安裝

  5.2 Preparation and installation of cable supports

  5.2.10??本條文為強制性條文,必須嚴格執(zhí)行。為避免電纜發(fā)生故障時危及人身,金屬電纜支架、橋架、電纜豎井均必須可靠接地,較長時還應根據(jù)設計進行多點接地。

  5.2.10?? This provision is mandatory and must be strictly enforced. To avoid endangering personal safety in case of cable failure, metal cable supports, cable trays, and cable shafts must be reliably grounded, and multiple grounding points should be carried out according to the design for longer periods of time.

  根據(jù)上面的標準相關條文,可將電纜橋架接地的要求總結如下:

  According to the relevant provisions of the national standards above, the requirements for grounding cable trays can be summarized as follows:

  1、鋼制電纜橋架的起始端和終端必須與建筑物的接地裝置可靠連接。

  1. The starting and ending ends of steel cable trays must be reliably connected to the grounding device of the building.

  2、當鋼制電纜橋架全長大于30米時,每隔20-30米應設置一個接地連接點。

  2. When the total length of the steel cable tray is greater than 30 meters, a grounding connection point should be set every 20-30 meters.

  3、在伸縮縫或連續(xù)鉸鏈連接處,應使用小截面積為16mm2的銅軟導線或編織銅線連接。

  3. At expansion joints or continuous hinge connections, copper flexible wires or braided copper wires with a minimum cross-sectional area of 16mm2 should be used for connection.

  4、鋼制電纜橋架應與保護聯(lián)結導體可靠連接,全長不應少于2處接地。

  4. The steel cable tray should be reliably connected to the protective bonding conductor, and the total length should not be less than 2 grounding points.

  5、高分子合金電纜橋架、玻璃鋼橋架可以不接地。

  5. Polymer alloy cable trays and fiberglass cable trays may not be grounded.

  6、為避免電纜故障時危及人身,鋼制電纜橋架必須進行可靠接地,長距離橋架還應進行多點接地。

  6. To avoid endangering personal safety in case of cable failure, steel cable trays must be reliably grounded, and long-distance trays should also be grounded at multiple points.

  7、接地電阻不應大于1歐姆。

  7. The grounding resistance should not exceed 1 ohm.

  PART 2

  PART 2

  橋架為什么要接地

  Why do cable trays need to be grounded

  電纜橋架需要接地的主要原因是為了確保和可靠的電力傳輸。接地系統(tǒng)在電纜橋架中具有以下幾個重要作用:02

  The main reason why cable trays need to be grounded is to ensure safe and reliable power transmission. The grounding system plays the following important roles in cable trays:

  1、保護:接地系統(tǒng)能夠將電纜橋架上的電荷或電流通過接地導體釋放到地面,避免觸電事故的發(fā)生。

  1. Safety protection: The grounding system can release the charge or current on the cable tray to the ground through the grounding conductor, avoiding the occurrence of electric shock accidents.

  2、防止電磁干擾:電纜橋架可能會經(jīng)過電力設備或其他電磁干擾源附近。在這種情況下,沒有接地的電纜橋架可能會成為電磁干擾的傳導路徑,導致電纜信號的干擾和失真。通過接地,可以將干擾電流引導到地下,減少對電纜信號的干擾,確保信號傳輸?shù)目煽啃浴?/p>

  2. Preventing electromagnetic interference: Cable trays may pass near electrical equipment or other sources of electromagnetic interference. In this case, ungrounded cable trays may become a conductive path for electromagnetic interference, leading to interference and distortion of cable signals. By grounding, interference currents can be guided underground, reducing interference with cable signals and ensuring the reliability of signal transmission.

  3、靜電控制:當電纜橋架經(jīng)過干燥的環(huán)境或有靜電積聚的情況下,沒有接地的電纜橋架可能會產生靜電放電。這些靜電放電可能對敏感設備或人員造成損害。通過接地,可以有效地將靜電放電到地下,降低靜電對設備和人員的影響。

  3. Static control: When cable trays pass through dry environments or accumulate static electricity, ungrounded cable trays may generate static discharge. These electrostatic discharges may cause damage to sensitive equipment or personnel. By grounding, static electricity can be effectively discharged underground, reducing the impact of static electricity on equipment and personnel.

  4、電磁兼容性:電纜橋架作為電力和通信線纜的承載結構,其電磁輻射和敏感性對于其他設備和系統(tǒng)的正常運行可能具有影響。通過接地,可以減少電纜橋架本身的電磁輻射,并提高其與其他設備之間的電磁兼容性。

  4. Electromagnetic compatibility: As the load-bearing structure of power and communication cables, the electromagnetic radiation and sensitivity of cable trays may have an impact on the normal operation of other equipment and systems. By grounding, the electromagnetic radiation of the cable tray itself can be reduced, and its electromagnetic compatibility with other equipment can be improved.

  總而言之,接地是為了確保電纜橋架的運行,減少觸電風險,保護設備和人員免受電氣故障、電磁干擾和靜電等不良影響。

  In summary, grounding is to ensure the safe operation of cable trays, reduce the risk of electric shock, and protect equipment and personnel from adverse effects such as electrical faults, electromagnetic interference, and static electricity.

  本文由 山東電纜橋架 友情奉獻.更多有關的知識請點擊   http://m.h3022.cn  真誠的態(tài)度.為您提供為的服務.更多有關的知識我們將會陸續(xù)向大家奉獻.敬請期待.

  This article is a friendly contribution from Shandong Cable Bridge For more related knowledge, please click http://m.h3022.cn Sincere attitude To provide you with comprehensive services We will gradually contribute more relevant knowledge to everyone Coming soon.

 
qq
售前咨詢熱線
15168870138
售后咨詢熱線
13465410318
主站蜘蛛池模板: 全自动包装机_灌装机生产厂家-迈驰包装设备有限公司 | 南京交通事故律师-专打交通事故的南京律师 | 槽钢冲孔机,槽钢三面冲,带钢冲孔机-山东兴田阳光智能装备股份有限公司 | 深圳市宏康仪器科技有限公司-模拟高空低压试验箱-高温防爆试验箱-温控短路试验箱【官网】 | 鹤壁创新仪器公司-全自动量热仪,定硫仪,煤炭测硫仪,灰熔点测定仪,快速自动测氢仪,工业分析仪,煤质化验仪器 | 钢结构厂房造价_钢结构厂房预算_轻钢结构厂房_山东三维钢结构公司 | 双吸泵,双吸泵厂家,OS双吸泵-山东博二泵业有限公司 | 扫地车厂家-山西洗地机-太原电动扫地车「大同朔州吕梁晋中忻州长治晋城洗地机」山西锦力环保科技有限公司 | 诺冠气动元件,诺冠电磁阀,海隆防爆阀,norgren气缸-山东锦隆自动化科技有限公司 | CTP磁天平|小电容测量仪|阴阳极极化_双液系沸点测定仪|dsj电渗实验装置-南京桑力电子设备厂 | 体视显微镜_荧光生物显微镜_显微镜报价-微仪光电生命科学显微镜有限公司 | 宁夏活性炭_防护活性炭_催化剂载体炭-宁夏恒辉活性炭有限公司 | 东莞螺杆空压机_永磁变频空压机_节能空压机_空压机工厂批发_深圳螺杆空压机_广州螺杆空压机_东莞空压机_空压机批发_东莞空压机工厂批发_东莞市文颖设备科技有限公司 | HYDAC过滤器,HYDAC滤芯,现货ATOS油泵,ATOS比例阀-东莞市广联自动化科技有限公司 | 食品无尘净化车间,食品罐装净化车间,净化车间配套风淋室-青岛旭恒洁净技术有限公司 | 外观设计_设备外观设计_外观设计公司_产品外观设计_机械设备外观设计_东莞工业设计公司-意品深蓝 | 灌装封尾机_胶水灌装机_软管灌装封尾机_无锡和博自动化机械制造有限公司 | 升降机-高空作业车租赁-蜘蛛车-曲臂式伸缩臂剪叉式液压升降平台-脚手架-【普雷斯特公司厂家】 | 水厂自动化|污水处理中控系统|水利信息化|智慧水务|智慧农业-山东德艾自动化科技有限公司 | 工装定制/做厂家/公司_工装订做/制价格/费用-北京圣达信工装 | 小威小说网 - 新小威小说网 - 小威小说网小说搜索引擎 | 硫化罐_蒸汽硫化罐_大型硫化罐-山东鑫泰鑫智能装备有限公司 | 真空包装机-诸城市坤泰食品机械有限公司 | 机床主轴维修|刀塔维修|C轴维修-常州翔高精密机械有限公司 | 珠海冷却塔降噪维修_冷却塔改造报价_凉水塔风机维修厂家- 广东康明节能空调有限公司 | 通用磨耗试验机-QUV耐候试验机|久宏实业百科 | 山东限矩型液力偶合器_液力耦合器易熔塞厂家-淄博市汇川源机械厂 | 广西绿桂涂料--承接隔热涂料、隔音涂料、真石漆、多彩仿石漆等涂料工程双包施工 | 课件导航网_ppt课件_课件模板_课件下载_最新课件资源分享发布平台 | 深圳APP开发公司_软件APP定制开发/外包制作-红匣子科技 | 苏州工作服定做-工作服定制-工作服厂家网站-尺品服饰科技(苏州)有限公司 | 瓶盖扭矩仪(扭力值检测)-百科| 热工多功能信号校验仪-热电阻热电偶校验仿真仪-金湖虹润仪表 | 福尔卡(北京)新型材料技术股份有限公司 | 平面钻,法兰钻,三维钻-山东兴田阳光智能装备股份有限公司 | 南昌旅行社_南昌国际旅行社_南昌国旅在线 | 西装定制/做厂家/公司_西装订做/制价格/费用-北京圣达信西装 | 深圳激光打标机_激光打标机_激光焊接机_激光切割机_同体激光打标机-深圳市创想激光科技有限公司 深圳快餐店设计-餐饮设计公司-餐饮空间品牌全案设计-深圳市勤蜂装饰工程 | 数码听觉统合训练系统-儿童感觉-早期言语评估与训练系统-北京鑫泰盛世科技发展有限公司 | 金环宇|金环宇电线|金环宇电缆|金环宇电线电缆|深圳市金环宇电线电缆有限公司|金环宇电缆集团 | 最新电影-好看的电视剧大全-朝夕电影网|